Product - GENY - YC2000A Single Phase Portable Standard Meter

 

GENY - YC2000A
 

The YC2000A is a portable standard designed for the test of single phase electricity meters in the field or in the lab and of three phase meters phase by phase

 

Features

    * With 3.5 inch 320×240 dot TFT color screen
    * Wide voltage supply range: 50V~420V
    * Wide current testing range: CCT test 500:1 dynamic range
    * Connection with current clamp: standard 100A. From 5A to 500A current as option.
    * Two ways for power supply: external AC power supply or test lead power supply

 

Functions

    * Measuring mode: gives the parameters of the line under test:
         voltage, current, phase angle
         active power, reactive power, apparent power
         power factor
         frequency
    * Waveform: show the wave form of voltage and current
    * Harmonics: make a graphic and numeric analysis of the THD. (2nd~51st)
    * Meters test: Performs the test to the meters. The data field configurable in this function is the serial number, the meter type, the constant, the divisor factor (for HF), the type of test and cycles.
    * CT ratio test: get CT ratio by synchronously testing primary and secondary current of CT
    * Energy accumulating: accumulate active and reactive energy in a setting time, used for meter's dial test
    * Test data storage: can store 1000 data groups. Data include meter type, serial number, constant, error, date, etc
    * Download the testing program: can download 1000pcs testing planning to the equipment, convenient for local use

 

Technical Specification

Accuracy grade                          Current clamp: 0.3% (active), 0.5% (reactive)
Test voltage range                    10V-300V
Test current range                     5A, 100A, 500A, 1000A, 2000A (current clamp)
Phase measurement               0°-360°
Frequency measurement        45Hz-65Hz
Harmonic measurement         2nd -51st
Power supply                             50V-420V
Power consumption                 <3W
Dimension(W×H×D)                190mm×140mm×50mm
Weight                                         0.7 kg